MODEL | Unit | GL6000 |
Type | – | Rotating field single-phase AC generator |
Frequentcy | Hz | 50 |
Standby Output | kVa [kW] | 6.0 [6.0] |
Prime Ouput | kVa [kW] | 5.5 [5.5] |
Voltage – Single Phase | V | 220 |
Voltage – Three Phase | V | – |
Amateur Connection | – | series |
Phase / Wire | – | 1/2 |
Power Factor | – | 1.0 |
No. of Poles | – | 2 |
Insulation | Class | Rotor coil : class F ; Stator coil : class B |
Voltage Regulation | % | 5.0 [ No load to full load ] |
Type of Coupling | – | Direct coupled |
AMPS | | |
Single Phase 110V | A | – |
Single Phase 220V | A | 25.0 |
Single Phase 240V | A | – |
Three Phase 380V | A | – |
Three Phase 415V | A | – |
NO. OF RECEPTACLES | | |
6 – 15 R | A | 2 |
TERMINAL | | |
Terminal | – | Available |
KUBOTA DIESEL ENGINE | | |
Type | – | Vertical, water-cooled, 4-cyled diesel engine |
Model | – | Z482 |
No. of Cylinders | – | 2 |
Bore x Stroke | mm [in.] | 67.0 x 68.0 [ 2.60 x 2.70 ] |
Displacement | LL [cu. in.] | 0.479 [ 29.2 ] |
Engine Speed | rpm | 3000 |
Continues Rated Output | kW [HP] | 6.9 [ 9.3 ] |
Lubricant [ API classification ] | – | Above CD grade |
Oil Capacity | L [qts.] | 2.2 [ 2.32 ] |
Coolant Capacity | L [qts.] | 3.7 [ 3.92 ] |
Starting System | – | Electric – 12 volt DC |
SET | | |
Fuel | | Diesel fuel No.2 [ ASTM D975 ] |
Fuel Consumption | | |
at 100% Load | L/h [gal./h] | 2.2 [ 0.58 ] |
at 75% Load | L/h [gal./h] | 1.8 [ 0.48 ] |
at 50% Load | L/h [gal./h] | 1.5 [ 0.39 ] |
at 25% Load | L/h [gal./h] | 1.2 [ 0.31 ] |
Fuel Tank Capacity | L [gal./h] | 28.0 [ 7.4 ] |
Continous Operation Hours | | |
at 100% Load | h | 12.0 |
at 75% Load | h | 15.6 |
at 50% Load | h | 18.7 |
at 25% Load | h | 23.3 |
Battery [Ah/5h] | – | 12V [ 28Ah ] |
Dimensions | mm | 1066 x 618 x 698 |
[ L x W x H ] | [in.] | [ 42.0 x 24.3 x 27.5 ] |
Approx. Net Weight | kg [lbs] | 235 [ 518 ] |
Sound Level [ Full load at 7 m ] | dB [A] | 65 |
Emergency Stop System | | in case of abnormal : Oil pressure, water temperature, or when the access terminal cover is opened. |